SELV (short for “Safety Extra Low Voltage” – formerly also referred to as safety extra-low voltage) describes a voltage that is chosen to be low enough so that direct contact poses no danger from excessive body currents, both under intended operating conditions and in the event of a single fault.
In the event of an insulation failure, adequate protection must still be provided. In power supply units, this is achieved through galvanic isolation with double or reinforced insulation between the primary and secondary sides. No additional protection against direct contact is required.
Under intended operating conditions in dry locations, the voltage of a SELV power source must not exceed a peak value of 42.4 V for AC or superimposed AC voltage, and must not exceed 60 VDC for DC voltage.
In the event of a single fault, the specified voltage limits must not be exceeded for longer than 200 ms. Furthermore, the peak value of 71 V for AC voltage and the DC voltage value of 120 VDC must not be exceeded. Grounding of the secondary side is not required, but permissible.
See also PELV.
← WikiLED A–Z
WikiLED · LED-Glossar
SELV
SELV (short for "Safety Extra Low Voltage" – formerly also referred to as safety extra-low voltage) describes a voltage that is chosen to be low enough so that direct contact poses no danger under intended operating conditions …